NFPA 110 Fuel Testing for Emergency and Standby Generators
Facilities that depend on diesel-powered emergency and standby generators need fuel that will start the engine and carry the load when normal power fails. NFPA 110, Standard for Emergency and Standby Power Systems, sets a clear minimum for that fuel. In section 8.3.7, the standard requires a fuel quality test at least annually, using appropriate ASTM standards.
DR FUEL CLEAN INC, based in Baltimore since 2002, provides NFPA 110 generator fuel testing for hospitals, data centers, and other facilities that operate Level 1 or Level 2 Emergency Power Supply Systems (EPSS). Samples analyzed by ISO/IEC 17025-accredited laboratories. You receive a written report you can keep with your inspection and maintenance records.
The authority having jurisdiction (AHJ) may adopt a specific edition of NFPA 110, and your facility program or engine manufacturer may require more frequent testing or additional methods. Confirm the edition and any local rules that apply to your site.
Who this testing is for
This service is for hospitals, data centers, and other sites whose backup power is an NFPA 110 Level 1 or Level 2 EPSS.
Under NFPA 110, Level 1 systems are those where failure of the emergency power supply could result in loss of life or serious injury. Level 2 systems are those for which a failure is less critical to life safety, but the generator is still relied on when the normal electrical source is lost. Stored diesel is part of that power system, and annual fuel quality testing belongs in the same maintenance file as your generator exercise records.
What NFPA 110 section 8.3.7 requires
The requirement most widely cited from current editions of NFPA 110 is this: a fuel quality test shall be performed at least annually using appropriate ASTM standards.
- At least annually is a minimum. It is a floor, not a complete fuel-management program. Some facilities test more often because contamination can develop between annual tests.
- Section numbers can differ by edition. Current editions place this requirement in section 8.3.7. In the 2010 edition, which some AHJs still enforce, it is numbered 8.3.8. Verify the edition adopted at your site before citing a section number in a compliance file.
- “Appropriate ASTM standards” are not a single named package. The standard requires suitable ASTM methods. It does not publish one universal test panel. Your AHJ, engine manufacturer, or written facility procedure may specify which methods to use.
Some later editions also refer to the manufacturer’s recommendations alongside ASTM methods. Confirm the exact wording in the edition that applies to your facility.
Annex A.8.3.7: ASTM D975 and bottom-of-tank sampling
NFPA 110 annex material is advisory guidance, not a second set of mandatory rules. Annex A.8.3.7 still matters: it points to ASTM D975, Standard Specification for Diesel Fuel Oils, and calls for special attention to sampling the bottom of the storage tank for water, sediment, and microbial growth, so the stored fuel is as clean and dry as practicable.
Water, sludge, and microbial debris settle. A sample taken from the middle or top of the tank can describe the bulk fuel while missing the contamination that will be drawn toward the pickup, filters, and injectors when the generator runs.
Why stored fuel often needs more than a delivery specification
ASTM D975 is the widely used specification for diesel fuel oils. Unless the buyer and supplier agree otherwise, it prescribes the required properties of diesel fuel at the time and place of delivery. Meeting selected D975 properties at delivery is not the same as proving that fuel still stored in a standby tank months or years later remains suitable for an emergency run.
In storage, diesel can oxidize, pick up water, support microbial growth at the fuel-water interface, and accumulate particulate matter. Stored generator fuel is therefore often also tested for:
- Microbial contamination
- Karl Fischer water (a direct measurement of water content)
- Oxidation stability
- Particulate contamination, often reported as an ISO cleanliness count
These methods help show how fuel has changed in the tank. They do not replace the ASTM methods your AHJ or manufacturer expects, and they are not a guaranteed “NFPA 110 package.” The right slate depends on the fuel, the tank, and the requirements that apply to your site.
DR Fuel Clean’s diesel fuel testing services can include ASTM D975 parameters such as flash point, cetane, distillation, sulfur, and sediment and water, along with microbiological testing and ISO particulate cleanliness.
Request testing to schedule annual NFPA 110 generator fuel testing, or call (410) 490-5933.
How often should generator fuel be tested?
NFPA 110 requires a fuel quality test at least once a year. That is the code minimum, not always the most conservative schedule for a hospital, data center, or other Level 1 or Level 2 site.
Testing beyond that minimum depends on fuel age, tank condition, temperature and humidity, whether the fuel turns over, and what prior results have shown. If earlier analysis found water, microbes, or degradation, more frequent follow-up is often warranted until results stabilize. Facility policies and AHJ requirements may also be tighter than the annual floor.
For a fuller discussion of testing frequency for stored diesel at critical facilities, see How Often Should You Test Your Stored Diesel Fuel?.
When fuel is off specification
If testing shows that stored diesel is outside the acceptable range, the fuel is typically restored by polishing, treatment, or replacement.
Fuel polishing circulates stored diesel through filtration and water separation to remove water, sediment, and loose contamination and return usable fuel to the tank. Tank cleaning addresses sludge, biofilm, and deposits on the tank itself, which polishing alone may not solve. Treatment, including additive use when it is appropriate, can be part of the same plan. After the work, the fuel should be tested again so the file shows the condition that remains in the tank.
See our service capabilities page for mechanical polishing, water and contaminant extraction, and tank interior cleaning.
How to request testing
Fuel testing is available nationwide by mail-in from anywhere in the United States (shipping kits are available). On-site sampling is offered primarily along the East Coast, from North Carolina to Maine; contact us for extended coverage. Most standard analyses are completed with a 72-hour turnaround. The report provides clear, actionable findings and recommended next steps, including whether polishing, treatment, tank cleaning, or replacement should be considered.
Frequently asked questions
How often does NFPA 110 require generator fuel testing?
NFPA 110 requires a fuel quality test at least annually using appropriate ASTM standards (section 8.3.7 in current editions; section 8.3.8 in the 2010 edition). That annual test is a minimum. Your AHJ, engine manufacturer, or facility program may require more frequent testing.
Is ASTM D975 enough to satisfy the annual fuel quality test?
ASTM D975 is the standard specification for diesel fuel oils and is the specification annex A.8.3.7 points to. It prescribes required properties at delivery, unless the parties agree otherwise. NFPA 110 requires testing with appropriate ASTM standards; it does not name one mandatory panel. Stored fuel is often also tested for microbial growth, Karl Fischer water, oxidation stability, and particulates. Confirm the methods your AHJ and manufacturer expect.
Why does bottom-of-tank sampling matter?
Annex A.8.3.7 advises paying special attention to sampling the bottom of the storage tank for water, sediment, and microbial growth. Those contaminants settle. A mid-tank or upper sample can miss the material that will reach filters and injectors when the generator runs.
What additional tests are often used for stored generator fuel?
Beyond D975 delivery properties, stored diesel is often also tested for microbial contamination, Karl Fischer water, oxidation stability, and particulate contamination (including ISO cleanliness). The exact slate should match the fuel, the tank, and the requirements that apply to your site.
What happens if generator fuel fails the test?
Off-specification fuel is typically corrected by polishing, treatment, or replacement. Tank cleaning may be needed when sludge, biofilm, or deposits remain in the tank. The fuel should be retested after remediation so your records reflect the restored condition.
Who should use NFPA 110 generator fuel testing?
Hospitals, data centers, and other facilities that operate Level 1 or Level 2 emergency or standby generators (EPSS) under NFPA 110. Level 1 systems are those where failure could result in loss of life or serious injury; Level 2 systems are less critical to life safety but still rely on backup power when the normal source is lost.
Request testing or call (410) 490-5933 to schedule NFPA 110 generator fuel testing.